GLASS
BLOCK IN NON-MASONRY WALLS
WITH PANEL ANCHOR CONSTRUCTION
Rating: 45 or 60 minutes
1.
Steel studs below sill to be 3-5/8" x 20 gauge
@ 8" o.c. (Max. length of 36") with a 3-5/8"
x 20 gauge runner channel to create base for glass block.
2.
Each jamb to be 3-5/8" x 20 gauge steel stud and
runner channel. Gypsum board to be installed between stud and
runner channel.
3.
Head to be (2) 3-5/8" x 20 gauge studs with (2)
runner channels.
4.
Panel anchors to be 1-3/4" x 20 gauge x 24"
long galvanized steel. Locate above first course and in every
other pint above. Do not locate in joint below top course. If
necessary, locate in second joint below top course. Secure panel
anchor with (2) self drilling, self tapping screw fasteners.
Fasteners to be located at the top of slots and immediately
above bend of the panel anchor. Install panel anchors at head
in every other vertical mortar pint.
5.
Horizontal mortar joints with panel anchors to be reinforced
with 9 x 14 AWG galvanized wire. Overlap panel anchor a minimum
of 6". Use Type S mortar.
6.
Fill space between glass block and channel with glass
fiber, mineral wool or polyethylene and seal with silicone caulk.
7.
Accuspeed or A.B. Kreuz spacers may be used to install
Weck Glass Block.
GLASS
BLOCK IN NON-MASONRY WALLS
WITH CHANNEL CONSTRUCTION
Rating: 45 or 60 minutes
1.
Steel studs below sill to be 3-5/8" x 20 gauge
@ 8" o.c. (Max. length of 36") with a 3-5/8"
x 20 gauge runner channel to create base for glass block.
2.
Each jamb to be 3-5/8" x 20 gauge steel stud and
runner channel with 14 gauge channel secured @ 16" o.c..
3.
Head conditions similar to jamb for interior installations.
Channel at sill is optional.
4.
Horizontal reinforcing for Standard Series block (3-7/8"
thick) to be 2" wide consisting of two 9 gauge parallel
wires with cross ties @ 8" o.c.. Reinforcing for Thinline
Series block to be 1-5/8" wide. All reinforcing to have
hot dipped zinc coating. Horizontal reinforcing to have a minimum
spacing of 18" o.c., i.e. Every third joint at 6"
block and every other joint at 8" block.
5.
Glass block to be placed 1" deep into recess.
Recess to be formed of 1-3/4" deep steel channel. Steel
channel to be 14 gauge below metal. Do not use channel at sill
for exterior installations.
6.
Fill space between glass block and channel with glass
fiber, mineral wool or polyethylene and seal with silicone caulk.
7.
Accuspeed or A.B. Kreuz spacers may be used to install
Weck Glass Block. |